制造商型号: S803HV-K3
制造商: ABB
产品描述: 塑料外壳式断路器 2CCF020070R0001
ABB EcoSolutions:
Yes
Recyclability Rate of the Product acc. to EN45555:
Design for Closing Resource Loops - Standard EN45555 - 86.29 %
ABB Site Meeting Group Waste To Landfill Target:
No non-hazardous waste is sent to a landfill
End Of Life Disassembling Instructions:
9AKK108470A2575
Environmental Product Declaration - EPD:
EPD ABBG-00659-V01.01-EN_G - S800 MCB
EPD ABBG-00658-V01.01-EN_E - S800 MCB
Technical
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(1000 V AC) 1.5 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
(1000 V AC) 1.5 kA
Contact Position Indication:
ON / OFF / TRIP
Energy Limiting Class:
3
Number of Protected Poles:
3
Number of Poles:
3P
Tightening Torque:
3.5 N·m
Actuator Marking:
I / O
Recommended Screw Driver:
Pozidriv 2
Accessories Available:
Yes
Remarks:
Connection from top and bottom
Connecting with CU only
IP40 in enclosure with cover
Cage terminal with captive screw
Connecting Capacity:
Flexible 0 … 50 mm²
Rigid 0 … 70 mm²
Terminal Type:
Screw Terminals
Electrical
Tripping Characteristic:
K
Rated Operational Voltage:
acc. to IEC 60947-2 1000 V AC
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 1000 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Input Voltage Type:
AC
Rated Current (In):
3 A
Rated Frequency (f):
50/60 Hz
Power Loss:
7.2 W
at Rated Operating Conditions per Pole 2.4 W
Overvoltage Category:
III
Design
Housing Material:
Insulation group I, RAL 7035
Material Compliance
RoHS Information:
RoHS_confirmation_22072019
EU Declaration of Conformity - S800 S-UC, HV, PV-SP
RoHS Status:
Following EU Directive 2011/65/EU
RoHS Date:
20170426
REACH Declaration:
REACH Declaration for S800 and its accessories
REACH Information:
False - does not contain substances > 0.1 mass percentage
REACH Date:
20200527
Conflict Minerals Reporting Template (CMRT):
Conflict Minerals Reporting Template
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Business
Environmental
Ambient Air Temperature:
Operation -25 ... +60 °C
Storage -40 ... +70 °C
Degree of Protection:
IP20
Pollution Degree:
2
Resistance to Vibrations:
1 mm 7 - 13.2 Hz
0.7g with Load 100% x Ie 13.2 - 100 Hz
Environmental Information:
Environmental information S800 and accessories
Dimensions
Width in Number of Modular Spacings:
4.5
Product Net Width:
81 mm
Product Net Height:
142 mm
Product Net Depth / Length:
82.5 mm
Product Net Weight:
720 g
Built-In Depth (t2):
82.5 mm
Ordering
Package Level 1 Units:
box 1 piece
Package Level 1 Gross Weight:
850 g
Certificates and Declarations
Declaration of Conformity - CE:
EU Declaration of Conformity - S800 S-UC, HV, PV-SP
Installation
Instructions and Manuals:
Instruction Manual S800 range
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position:
Any
Popular Downloads
Data Sheet, Technical Information:
Global Product Catalogue 2024 - MCBs
Global Product Catalogue 2024 - Accessories for MCBs and RCDs
Global Technical Details 2024 - MCBs
External Classifications and Standards
ETIM 9:
EC000042 - Miniature circuit breaker (MCB)
eClass:
V11.0 : 27141901
Object Classification Code:
F
Standards:
IEC/EN 60947-2
UL 1077